Mikster DLM-080 Manual do Utilizador Página 35

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 48
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 34
The DLM-080 FUTURE Digital Recorder – User’s Manual
26.11.2004
35
Function 4 (Recorder Register Reading)
Master >>> Slave
Byte
number
Value / variable
Definition
1 ADDEV Slave address in the rs485 network (range
1..32)
2 04 (04h ) Function number
3 Adres_h (h) address of the beginning of currently
read out register block
4 Adres_l (l) address of the beginning of currently
read out register block
5 Długość_H
6 Długość_l
Number of two-byte registers
7 CRC_h
8 CRC_l
Control total CRC-16
Master <<< Slave
Byte
number
Value / variable
Definition
1 ADDEV Slave address in the rs485 network (range
0..31)
2 04 (04h ) Function number
3 ByteCNT Byte counter
4 Rej 0
5 rej 1
. . . . .
n+2 rej n
Block of data (registers) determined by start
address and data volume in a frame sent by
MASTER device
n+3 CRC_H
n+4 CRC_L
Control total