The DLM-080 FUTURE Digital Recorder – User’s Manual
26.11.2004
12
f) an hour-meter (range from 0 to 999)
g) multivibrator (second or minute or hour base)
4.1 THE PT-100 MEASUREMENT CHANNEL
In case if a measurement channel is defined as PT-100, readout values will be displayed in
a dynamic way, that is:
• within range from -99.9 to -10.0 with accuracy of 1 °C
• within range from -9.9 to +99.9 with accuracy of 0.1 °C
• within range from +100.0 to +399.9 with accuracy of 1 °C
4.2 THE 0..20 (4..20) mA MEASUREMENT CHANNEL
In case if a measurement channel is defined as 0..20 (4..20) mA, readout values will be
displayed according to the value of the F54-F61(SETUP) function.
that is:
• if F54-F61 = 3, then display range is 0.00 to 9.99 (0..20 mA)
• if F54-F61 = 4 , then display range is 00.0 to 99.9 (0..20 mA)
• if F54-F61 = 5 , then display range is 000 to 999 (0..20 mA)
• if F54-F61 = 6 , then display range is 0.00 to 9.99 (4..20 mA)
• if F54-F61 = 7 , then display range is 00.0 to 99.9 (4..20 mA)
• if F54-F61 = 8 , then display range is 000 to 999 (4..20 mA)
4.3 CHANNEL AS TIME-METER
In case if a measurement channel is defined as time-meter, then method of time metering
will be defined in the F38-F40 (SETUP) functions, that is:
• if F54-F61 = 11
, then second-meter
• if F54-F61 = 12
, then minute-meter
• if F54-F61 = 13
, then hour-meter
Moreover, it is necessary to define in the F62-F69 functions the method for time-meter
release, that is:
• F62-F69 = 0 time-meter reset, and it is released “manually” after pressing and
holding the
key (for proper channel) for approximately 2[s].
• F62-F69 = 1
then, if Tini contact closed, time-meter counts down until reaching
the set value, if time-meter reaches the set value and Tini contact opens, then the