The DLM-080 FUTURE Digital Recorder – User’s Manual
26.11.2004
11
3.5.3 Measurement channel tuning procedure for the 0..20,4..20mA input
1
- select channel to tune by pressing the keys in channel 1
display field.
2 - preset model signal value, e.g. 20mA
3 - enter indicated value for 0 mA (4 mA) current by pressing the
keys in channel 4 display field.
4 - enter indicated value for model signal by pressing the keys in
channel 6 display field (e.g. 20 mA )
5
- as soon as the above-mentioned operations are complete, carry out correction of
amplification by pressing the
key in channel 2 display field.
(in order to cancel the correction press the key in channel 2 display field)
completed correction will be indicated by blinking of the diode built-in in the
key in channel 2 display field.
Attention ! Do not carry out correction of zero for the 0..20 mA, 4..20 mA input !
3.5.3 Saving corrections in memory, exiting the SERVICE mode
Press the key in order to exit the service mode and to save correction value.
4. THE DLM-080 RECORDER MEASUREMENT AND CONTROL
CHANNELS
The DLM-080 Recorder enables to define channel type for each of the channels as:
a) the PT-100 measurement channel (measurement range from -99.9 to +399.9° C, scale
interval 0.1 ° C)
b) the 0..20 mA measurement channel (measurement range from -99 to 999)
c) the 4..20 mA measurement channel (measurement range from -99 to 999)
d) a second-meter (range from 0 to 999)
e) a minute-meter (range from 0 to 999)